Maximum Syn time
Figure 848: Determination of the checking time for closing
CBXCBR receives information about the circuit breaker status and thus is able
to adjust the command signal to be delivered to the Synchro check function. If
the external command signal CL_COMMAND is kept active longer than necessary,
the
CMD_FAIL_AL
alarm output is activated. The alarm indicates that the control
module has not removed the external command signal after the closing operation.
To avoid unnecessary alarms, the duration of the command signal should be set in
such a way that the maximum length of the signal is always below
Maximum Syn
time + 5s.
Close pulse
Maximum Syn time
5s
Figure 849: Determination of the alarm limit for a still-active command signal
Closing is permitted during
Maximum Syn time, starting from the moment the
external command signal
CL_COMMAND
is activated. The
CL_COMMAND
input must
be kept active for the whole time that the closing conditions are waited to be
fulfilled. Otherwise, the procedure is cancelled. If the closing-command conditions
are fulfilled during
Maximum Syn time, a
SYNC_OK
pulse is delivered to the circuit
breaker function. If the closing conditions are not fulfilled during the checking time,
the alarm
CL_FAIL_AL
is activated as an indication of a failed closing attempt.
The
SYNC_OK
pulse is not delivered if the closing conditions become valid after
Maximum Syn time has elapsed. The closing pulse is delivered only once for
Control functions
1MRS759142 F
1550
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......