f
VoltagedipTm
slip
≤
−
⋅
(
)
π
δ
π
0
(Equation 275)
f
slip
Slip frequency
δ
0
Swing angle at the outer blinder
VoltagedipTm
Set
V dip time
Otherwise,
OPERATE
is activated on the way out, when the impedance exits an outer
blinder and the swing repeats for the set
Max number slips count in the respective
enabled zone that the swing has passed through.
If the
Swing time has elapsed but the impedance exits the inner blinder and
continues through the opposite blinders without passing through the mho circle,
the
SWING
output is activated. The
SWING
output remains activated for a time
determined by the
Reset time setting unless another swing occurs before the reset
time expires causing the output to remain active for another
Reset time interval. If
this swing is repeated for the set
Max Num slips Zn3 count and the Zone 3 enable
setting is “Yes”, the
SWING_OP
output is activated. The
SWING_OP
output remains
activated for a time determined by the
Operate dropout time setting.
If the “Adaptive” option is selected and an OSB condition is not detected, but
the impedance enters the mho circle after remaining between the inner and outer
blinders for greater than 1.5 cycles, the function assumes a severe swing and assert
the
OPERATE
output.
The drop out delay for
OPERATE
output can be set by
Operate dropout time setting.
If the polarity of the voltage signal is opposite to the normal polarity, the correction
can be done by setting
Voltage reversal to “Yes”, which rotates the impedance
vector by 180 degrees.
The
DISABLE
input can be used to coordinate the correct operation during the
start-up situation. The function is blocked by activating the DISABLE signal. Once
the DISABLE signal is deactivated, the function remains blocked (outputs disabled)
for additional time duration as set through the setting
Disable time.
Blocking logic
There are three operation modes in the blocking function. The operation modes
are controlled by the
BLOCK
input and the global setting in Configuration >
System > Blocking mode which selects the blocking mode. The
BLOCK
input can
be controlled by a binary input, a horizontal communication input or an internal
signal of the protection relay's program. The influence of the
BLOCK
signal activation
is preselected with the global setting
Blocking mode.
The
Blocking mode setting has three blocking methods. In the “Freeze timers”
mode, the operation timer is frozen to the prevailing value, but the
OPERATE
output
is not deactivated when blocking is activated. In the “Block all” mode, the whole
function is blocked and the timers are reset. In the “Block OPERATE output” mode,
the function operates normally but the
OPERATE
output is not activated.
1MRS759142 F
Protection functions
REX640
Technical Manual
1011
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......