Figure 803: Presentation of operating limits
The range information can also be decoded into boolean output signals on some
of the measuring functions and the number of phases required to exceed or
undershoot the limit before activating the outputs and can be set with the
Num
of phases setting in the three-phase measurement functions CMMXU and VMMXU.
The limit supervision boolean alarm and warning outputs can be blocked.
Table 1358: Settings for limit value supervision
Function
Settings for limit value supervision
Three-phase current measurement (CMMXU) High limit
A high limit
Low limit
A low limit
High-high limit
A high high limit
Low-low limit
A low low limit
Three-phase voltage measurement (VMMXU) High limit
V high limit
Low limit
V low limit
High-high limit
V high high limit
Low-low limit
V low low limit
Phase voltage measurement (VPHMMXU)
High limit
V high limit
Low limit
V low limit
High-high limit
V high high limit
Low-low limit
V low low limit
Single-phase voltage measurement (VAMM-
XU)
High limit
V high limit
Low limit
V low limit
High-high limit
V high high limit
Low-low limit
V low low limit
Residual current measurement (RESCMMXU) High limit
A high limit res
Table continues on the next page
Measurement functions
1MRS759142 F
1436
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......