Earth-fault distance calculation in case of compensated (resonant earthed)
networks where an earth-fault current raising resistor is used
In case of compensated (resonant earthed) networks where an earth-fault current
raising resistor is used, the setting
Flt Loc Det mode is equal to "Comp, switched R".
The algorithm for calculation of earth-fault distance requires a measurable change
in the measured phase currents and phase-to-earth voltages during an earth fault.
Such a change can be accomplished by switching on the resistor of the PAW winding
(Power Auxiliary Winding) of the compensation coil during the fault.
The algorithm requires three independent time instances, which are assumed to be
known by the algorithm:
• t
0
= time instance before the fault
• t
1
= time instance before the change during the earth fault
• t
2
= time instance after the change during the earth fault
The effect of loads is considered by applying “Load modelling” algorithm.
The required settings of the algorithm are:
• R1 = Positive-sequence resistance of the protected feeder [ohm, prim]
• X1 = Positive-sequence reactance of the protected feeder [ohm, prim]
• R0 = Zero-sequence resistance of the protected feeder [ohm, prim]
• X0 = Zero-sequence reactance of the protected feeder [ohm, prim]
• s = Equivalent load distance [pu]
Determining timings of changes: determination of earth fault occurrence and time
instance t0
Timing t
0
is needed to store the current and voltage phasors right before the
occurrence of the earth fault. Timing t
0
is common to both triggering types
(
Calculation Trg mode either “Internal” or “External”). Pre-fault (indicating healthy
network) phasors are continuously updated and stored at intervals of 300 ms until
the earth fault is indicated. When the earth fault is detected (internal detection), the
pre-fault phasor is stored at least 300 ms before the detection of the earth fault.
This time instance before the earth fault is noted as t
0
).
Determining timings of changes: determination of changes during an earth fault
due to parallel resistor switching, time instances t1 and t2
• Time instance t
1
equals the time during earth fault, right before the switching of
the parallel resistor of the coil (see
)
• Time instance t
2
equals the time during earth fault, just after the switching of the
parallel resistor of the coil (see
)
In case of external triggering, time instances t
1
and t
2
are determined using input
TRIGG_T
and delay setting
Time delay.
TRIGG_T
input should be activated when the
parallel resistor is switched ON. Time instance t
1
is taken at least one fundamental
cycle before
TRIGG_T
rising edge. Time instance t
2
is taken according to the set
Time delay after the rising edge of
TRIGG_T
signal. Setting
Time delay should be
few hundreds of ms and it is needed due to oscillations in currents and voltages
after the switching of the parallel resistor.
TRIGG_T
activation must be given after the initial earth-fault ignition
transients. Only one activation of
TRIGG_T
is allowed during an earth
fault. However, further activations are internally disabled.
1MRS759142 F
Protection related functions
REX640
Technical Manual
1201
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......