Parameter
Values (Range)
Unit
Step
Default
Description
Par line Comp zone
1
0=False
1=True
0=False
Enable parallel line
compensation for
PE-loops, zone 1
Mutual R0 zone 1
0.00...3000.00
ohm
0.01
40.00
Parallel line zero se-
quence mutual re-
sistance, zone 1
Mutual X0 zone 1
0.00...3000.00
ohm
0.01
40.00
Parallel line zero se-
quence mutual re-
actance, zone 1
Tilt angle zone 2
-45...45
deg
1
0
Tilt angle (posi-
tive value increases
zone area), zone 2
Par line Comp zone
2
0=False
1=True
0=False
Enable parallel line
compensation for
PE-loops, zone 2
Mutual R0 zone 2
0.00...3000.00
ohm
0.01
40.00
Parallel line zero se-
quence mutual re-
sistance, zone 2
Mutual X0 zone 2
0.00...3000.00
ohm
0.01
40.00
Parallel line zero se-
quence mutual re-
actance, zone 2
Tilt angle zone 3
-45...45
deg
1
0
Tilt angle (posi-
tive value increases
zone area), zone 3
Par line Comp zone
3
0=False
1=True
0=False
Enable parallel line
compensation for
PE-loops, zone 3
Mutual R0 zone 3
0.00...3000.00
ohm
0.01
40.00
Parallel line zero se-
quence mutual re-
sistance, zone 3
Mutual X0 zone 3
0.00...3000.00
ohm
0.01
40.00
Parallel line zero se-
quence mutual re-
actance, zone 3
Tilt angle zone 4
-45...45
deg
1
0
Tilt angle (posi-
tive value increases
zone area), zone 4
Par line Comp zone
4
0=False
1=True
0=False
Enable parallel line
compensation for
PE-loops, zone 4
Mutual R0 zone 4
0.00...3000.00
ohm
0.01
40.00
Parallel line zero se-
quence mutual re-
sistance, zone 4
Mutual X0 zone 4
0.00...3000.00
ohm
0.01
40.00
Parallel line zero se-
quence mutual re-
actance, zone 4
Tilt angle zone 5
-45...45
deg
1
0
Tilt angle (posi-
tive value increases
zone area), zone 5
Par line Comp zone
5
0=False
1=True
0=False
Enable parallel line
compensation for
PE-loops, zone 5
Mutual R0 zone 5
0.00...3000.00
ohm
0.01
40.00
Parallel line zero se-
quence mutual re-
sistance, zone 5
Mutual X0 zone 5
0.00...3000.00
ohm
0.01
40.00
Parallel line zero se-
quence mutual re-
actance, zone 5
Table 930: DSTPDIS Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
1=on
Operation Off / On
Table continues on the next page
1MRS759142 F
Protection functions
REX640
Technical Manual
993
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......