The closing angle is the estimated angle difference after the breaker closing delay.
The
Minimum Syn time setting time can be set, if required, to demand the minimum
time within which conditions must be simultaneously fulfilled before the
SYNC_OK
output is activated.
The measured voltage, frequency and phase angle difference values between
the two sides of the circuit breaker are available as monitored data values
U_DIFF_MEAS, FR_DIFF_MEAS and PH_DIFF_MEAS. Also, the indications of the
conditions that are not fulfilled and thus preventing the breaker closing
permission are available as monitored data values U_DIFF_SYNC, PH_DIF_SYNC
and FR_DIFF_SYNC. These monitored data values are updated only when the
Synchro check is enabled with the
Synchro check mode setting and the measured
ENERG_STATE is "Both Live".
Continuous mode
The continuous mode is activated by setting the parameter
Control mode to
"Continuous". In the continuous control mode, Synchro check is continuously
checking the synchronism. When synchronism is detected (according to the
settings), the
SYNC_OK
output is set to TRUE (logic '1') and it stays TRUE as long as
the conditions are fulfilled. The command input is ignored in the continuous control
mode.
SECRSYN
CBXCBR
I
Closing
permission
Closing
command
Figure 845: A simplified block diagram of the Synchro check function in the
continuous mode operation
Command mode
If
Control mode is set to "Command", the purpose of the Synchro check
functionality in the command mode is to find the instant when the voltages on both
sides of the circuit breaker are in synchronism. The conditions for synchronism are
met when the voltages on both sides of the circuit breaker have the same frequency
and are in phase with a magnitude that makes the concerned busbars or lines such
that they can be regarded as live.
In the command mode operation, an external command signal
CL_COMMAND
(initiated by the breaker function CBXCBR output
CL_REQ
), in addition to the normal
closing conditions, is needed for delivering the
SYNC_OK
signal for the breaker
function input
SYNC_OK
. If the closing conditions are fulfilled during a permitted
check time set with
Maximum Syn time, the Synchro check function delivers a
SYNC_OK
signal to the circuit breaker function after the command signal is delivered
for closing.
Control functions
1MRS759142 F
1548
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......