(Equation 112)
When setting
Enable harmonics = “Enable”:
(Equation 113)
Where is the magnitude of the n
th
harmonic negative-sequence current
component (n = 1, 2, 3, 5, 7 and 9).
In case of frequency adaptive system measurements, only 2
nd
, 3
rd
and 5
th
harmonics are calculated.
In case there is fault resistance included in the fault current path, the effect of fault
resistance is to decrease the value of earth-fault current as shown by
.
The downscaling of fault current magnitude can be estimated to be proportional
to the magnitude of per unit value of residual voltage, refer to
setting
Ena RF Compensation = “Enable”, user can compensate the effect of fault
resistance and then earth-fault current estimate becomes independent of actual
fault resistance value. This is done by dividing the fault current estimate with per
unit value of residual voltage (< 1pu):
Estimate for “fault resistance compensated” earth-fault current,
:
(Equation 114)
This means that with setting
Ena RF Compensation = “Enable”, regardless of actual
fault resistance magnitude, the earth-fault current estimate matches the value that
would be valid if the fault would be a galvanic one (fault resistance equals zero).
Thanks to this feature the fault is always seen and treated as a galvanic fault
regardless of possible fault resistance. This functionality allows acceleration of
protection operation speed during high(er) ohmic earth fault when fault current
magnitude is low.
In case IFPTOC is used to detect high(er) ohmic earth faults, all start
thresholds (
Voltage start value, EF current Str Val or Touch Vol Str Val)
must be set according to sensitivity requirements. Otherwise
Ena RF
Compensation may not be effective during actual high(er) ohmic earth
fault.
In case of setting
Ena RF Compensation = “Enable”, the effect of
harmonics are not taken into account i.e. fault current estimation is
based only on fundamental frequency component.
illustrates this concept: In the left-hand column is shown residual
voltage, phase currents and fault current estimate during a galvanic earth fault (R
F
= 0 ohm). During a galvanic fault U
o
equals system nominal phase-to-earth voltage
Protection functions
1MRS759142 F
592
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......