in terms of fault resistance depends also on the network parameters
(nominal voltage, damping and detuning) as described by
(Equation 126)
where U
PE
is the nominal phase-to-earth voltage [V], I
d
is the total system damping
[A], I
v
is the detuning [A], U
F
is setting
Touch Vol Str Val in primary volts and R
E
is
setting
Maximum earthing Ris in primary ohms.
When
Operating curve type = “Inverse time EN50522” is selected, then the
protection operate time as a function of estimated touch voltage
(taking
account the effect of
Reduction factor) is according to
:
(Equation 127)
In IFPTOC function, the preferred presentation of operation timer characteristics
is by plotting the protection operate time as a function of permissible/estimated
touch voltage as illustrated in
.
Consider next three examples with
Operating curve type = “Inverse time EN50522”:
Example 5a. Inverse time operation of IFPTOC, when
Operation principle = “Touch
voltage based”,
Operating curve type = “Inverse time EN50522” and setting UTp
multiplier = 1.0 is illustrated in
. Start value for operation is set to be 20 V
(setting
Touch Vol Str Val). IFPTOC is set to have minimum operate time 100 ms and
maximum operate time of 5000 ms (settings
IDMT stage Min Op Tm, IDMT stage
Max Op Tm). Maximum earthing resistance value encountered in the protected
feeder is set to be 10 ohms (setting
Maximum earthing Ris) and Reduction factor
= 1. For illustrating the operating speed requirement of protection, limits of touch
voltage durations defined in standard EN50522 are shown for reference.
Protection functions
1MRS759142 F
616
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......