Name
Type
Description
FALSE if the clock has not been synchronized
by an SNTP server.
Table 52: IEEE 1588v2 Output signals
Name
Type
Description
ALARM
BOOLEAN
Alarm status for clock synchronization.
TRUE if the current master’s accuracy is not
within 1μs or priority1 is bigger than that of
first secondary’s. Also TRUE if the external
master was lost and the protection relay it-
self acts as a master. Otherwise FALSE.
WARNING
BOOLEAN
Warning status for clock synchronization.
TRUE if a previously connected and stored
primary master has been lost. Otherwise
FALSE.
EXTCLKMSTR
BOOLEAN
Status of the protection relay's clock syn-
chronization.
TRUE if the protection relay has been
synchronized by an external master.
FALSE if the clock has not been synchronized
by an external master.
Table 53: IRIG-B Output signals
Name
Type
Description
ALARM
BOOLEAN
Alarm status for clock synchronization.
TRUE if the signal has been lost for a minute.
Otherwise FALSE.
WARNING
BOOLEAN
Warning status for clock synchronization.
TRUE if the signal connection is lost.
FALSE if the relay is synchronized to an IRIG-B
master.
EXTCLKMSTR
BOOLEAN
Status of the protection relay's clock syn-
chronization.
TRUE if the protection relay has been
synchronized to an IRIG-B master. Otherwise
FALSE.
Table 54: DNP3, Modbus, IEC 60870-5-101/104 and IEC 60870-5-103 Output signals
Name
Type
Description
ALARM
BOOLEAN
Alarm status for clock synchronization.
TRUE if the clock has not been synchronized
by the master.
Table continues on the next page
Basic functions
1MRS759142 F
126
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......