DEFL_START
(Forward)
DEFL_START
(Reverse)
Bus A
Bus B
3
3
Figure 715: Simplified functional diagram of the blocking scheme, external fault
The unblocking function used with the blocking function provides a possibility to
supervise the communication channel. In this case, the
CRL
output signal is used as
a local blocking signal.
The operation mode
Unblock mode = "Time window" is not
recommended as the blocking is activated only for 150 ms after the
guard signal disappears. This results in an unwanted operation of the
protection.
Directional comparison unblocking scheme DCUB
The unblocking function is a complementary logic which can be used together
with the permissive communication schemes. In the unblocking scheme, the
dependability of the permissive schemes is improved by using the loss of guard
signal from the communication equipment to create a
CRL
output signal locally. This
enables the permissive scheme to operate even if the communication channel is
interrupted or lost.
The unblocking function uses a carrier guard signal which must always be present.
The absence of the
CRG
signal for a time longer than the value of the
Loss of carrier
time setting generates a logical
CRL
signal. A communication failure shorter than
the value of the
Loss of carrier time setting is always ignored.
The unblocking function is configured with the
Unblock mode setting.
•
Unblock mode = "Off": The unblocking function is disabled.
•
Unblock mode = "Permanent": If the
CRG
signal disappears for a longer time
than defined in the
Loss of carrier time setting, the logical
CRL
signal is
generated. The
CRL
output signal remains active until the
CRG
signal reappears.
The communication failure is not signaled by the
LCG
output.
1MRS759142 F
Protection related functions
REX640
Technical Manual
1257
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......