
If the actual burden of the current transformer (S
a
cannot be
reduced enough to provide a sufficient value for F
a
, there are two alternatives.
• A current transformer with a higher rated burden S
n
can be chosen (which also
means a higher rated accuracy limit F
n
) or
• A current transformer with a higher nominal primary current I1
n
(but the same
rated burden) can be chosen.
Example 2
Assuming that the actions according to the current transformer with a
higher nominal primary current I1
n
(but the same rated burden) are taken
to improve the actual accuracy limit factor (F
a
):
I
rTR
= 1000 A
Rated secondary current of the transformer
I
rCT
= 1500 A
Rated primary current of the CT on the transformer secondary
side
F
n
= 30
Rated accuracy limit factor of the CT
F
a
= (I
rCT
/ I
rTR
) · F
n
Actual accuracy limit factor due to oversizing the CT
F
a
= (1500/1000) · 30 = 45
In differential protection it is important that the accuracy limit factors
(F
a
) at both sides of the phase CTs correspond with each other, that is,
the burdens of the CTs on both sides should be as equal as possible. If
high inrush or start currents with high DC components flow through the
protected object when it is connected to the network, special attention
should be paid to the performance and the burdens of the CTs and to the
settings of the function block.
4.3.3.9
Signals
TR3PTDF Input signals
Table 671: TR3PTDF Input signals
Name
Type
Default
Description
I3P1
SIGNAL
-
Three-phase currents
1
I3P2
SIGNAL
-
Three-phase currents
2
I3P3
SIGNAL
-
Three-phase currents
3
BLOCK
BOOLEAN
0=False
Block
BLK_OPR_LS
BOOLEAN
0=False
Blocks operate out-
puts from biased
stage
BLK_OPR_HS
BOOLEAN
0=False
Blocks operate out-
puts from instantane-
ous stage
Protection functions
1MRS759142 F
742
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......