It depends on the load characteristics how much the load is reduced as the voltage
drops. For instance, purely resistive loads are proportional to the square of the
voltage, whereas motor drives based on frequency controllers may draw constant
power despite small voltage changes.
The status of the
RSV
input can be read from the
RSV
input data.
9.10.5.6
Automatic voltage regulation of parallel transformers (Auto parallel)
A circulating current may occur between transformers if two or more transformers
with slightly different ratios are energized in parallel. This is due to the unbalanced
short circuit impedances of the parallel transformers. To avoid such currents, the
tap changers of the transformers should be adjusted to achieve equilibrium. If
the transformers are assumed identical, the tap (voltage) steps and tap positions
should also match. In this case, the Master/Follower principle can be used. However,
unequally rated transformers with different tap steps can be connected in parallel
and these configurations can also be managed by the tap changer control function.
For these configurations, the Minimizing Circulating Current (MCC) or Negative
Reactance Principle (NRP) should be used. MCC and NRP are also suitable for
identical transformers.
The circulating current, which is almost purely inductive, is defined as negative if
it flows towards the transformer. U
ci
is positive and the control
voltage U
p
rises as a result to the
RAISE_OWN
output signal activation if the
circulating current level is sufficient (
other parameters remain the same. As a result, the voltage rise should diminish
the circulating current.
LDC equation and parallel connection
The additional challenge in the parallel connection regarding LDC is to know the
total current which flows through the parallel transformers.
In the Master/Follower mode, it is easier to know the total current than in other
parallel modes since the transformers are assumed to have identical ratings, that
is, the total current (I
L
) is obtained by multiplying the measured
load current (the average of the currents I_A, I_B and I_C of the connected
own transformer) by the number of parallel transformers. OL5ATCC can internally
conclude the number of parallel transformers from the connected tap changer
position inputs. However, if there is no connected position information from
the other parallel transformers, the correct number of the parallel transformers,
excluding the own transformer, needs to be set with the
Parallel trafos setting.
In the MCC mode, the horizontal communication transfers the information from the
measured load currents between the regulators so that the total current needed in
the line drop compensation can be summed accurately. Here, I
L
is defined to be the
phasor sum of all the parallel power transformer currents. The currents from other
transformers must be fed via the
TR_I_AMPL
and
TR_I_ANGL
inputs of the OLGAPC
function.
In the NRP mode, the parallel transformers have different ratings and there is no
communication between the regulators. Therefore, when setting
Line drop V React
and
Line drop V Ris, the I
CT_n1
used in the equation should be the sum of the rated
currents of all the transformers operating in parallel. Here, I
L
is also defined as the
average of the currents (I_A, I_B and I_C). The calculated line drop compensation
value can be read from the monitored data LDC.
Control functions
1MRS759142 F
1706
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......