calculates the circulating current compensation term U
ci
(
) as in the
MCC.
U
I
I
U
ci
ci
n
n
=
−
⋅
⋅
Stability factor
100
(Equation 377)
I
ci
Circulating current
Stability
factor
Stability setting (the recommended value depends on the loop impedance)
If the transformers operating in parallel have different rated currents, the value of
the
Stability factor setting of the regulator should be proportional to the rated
currents, that is, the higher the rated current, the higher the
Stability factor setting
value.
It is possible to find out if the circulating current has been minimized by comparing
the reactive components of the currents measured by the different regulators. The
circulating current is minimized when the reactive components are equal.
The negative reactance method gives satisfactory results only if the phase angle of
the load current is known relatively accurately. If the actual phase angle deviates
from the phase angle setting, a regulating error occurs. However, if there is an
occasional stepwise change in the phase angle of the load, the regulating error can
be suppressed with the logic. This kind of stepwise change can occur, for example,
when a capacitor bank is switched on to compensate a reactive power flow. Another
possibility is to use an automatic setting group change between setting groups in
different loading situations. The setting groups then have different set values for
the load phase angle.
Minimizing Circulating Current MCC
The MCC principle is an optimal solution for controlling parallel transformers of
different ratings or step voltages in substations with varying reactive loads. Since
this control scheme allows the exchange of data between regulators, the circulating
current can be calculated more accurately than with other schemes. However,
a maximum of six regulators can be connected in parallel. To start the parallel
operation, the active operation mode parameter has to be set to "MCC" for all the
regulators of the connection. Furthermore, the signal
CON_STATUS
must indicate
that the transformers are connected to the network. A unit that minimizes the
circulating current must have the active operation mode set to "MCC". Units that
have the active operation mode set to "Manual" do not perform any circulating
current minimization operations themselves.
Control functions
1MRS759142 F
1710
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......