The activation of the
BLOCK
input blocks
MN_UNB_AL
output.
10.4.5.3
Percentile calculation
The Percentile calculation module performs the statistics calculation for the level
of voltage unbalance value for a settable duration. The operation of the Percentile
calculation module can be described with a module diagram.
Observation
period
Statistics
recorder
Percentile
calculator
PCT_UNB_AL
OBS_PR_ACT
BLOCK
10MIN_MN_UNB
(from Average calculator)
3s_MN_UNB
(from Average calculator)
Figure 980: Percentile calculation
10.4.5.4
Observation period
The Observation period module calculates the length of the observation time for
the Statistics recorder sub-module as well as determines the possible start of a new
one. A new period can be started by timed activation using calendar time settings
Obs period Str year, Obs period Str month, Obs period Str day and Obs period Str
hour.
The observation period start time settings
Obs period Str year, Obs
period Str month, Obs period Str day and Obs period Str hour are used
to set the calendar time in UTC. These settings have to be adjusted
according to the local time and local daylight saving time.
A preferable way of continuous statistics recordings can be selected over a longer
period (months, years). With the
Trigger mode setting, the way the next possible
observation time is activated after the former one has finished can be selected.
Table 1643: Trigger mode observation times
Trigger mode
Observation time
Single
Only one period of observation time is activated.
Periodic
The time gap between the two trigger signals is seven days.
Continuous
The next period starts right after the previous observation
period is completed.
The length of the period is determined by the settings
Obs period selection and
User Def Obs period. The
OBS_PR_ACT
output is an indication signal which exhibits
rising edge (TRUE) when the observation period starts and falling edge (FALSE)
when the observation period ends.
If the
Percentile unbalance, Trigger mode or Obs period duration settings change
when
OBS_PR_ACT
is active,
OBS_PR_ACT
deactivates immediately.
1MRS759142 F
Power quality measurement functions
REX640
Technical Manual
1851
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......