POSCLOSE
BLOCK
POSOPEN
OPR_ALM
OPR_LO
TRV_T_OP_ALM
TRV_T_CL_ALM
Switch
status
CLOSE_EXE
OPEN_EXE
RST_TRV_T
INVALIDPOS
MON_ALM
CLOSEPOS
OPENPOS
Inactivity
monitoring
Contact
travel time
Operation
counter
Figure 785: Functional module diagram
7.2.4.1
Switch status
This module monitors the position of the earthing switch or disconnector, that is,
whether the switch is in an open, closed, intermediate or faulty position.
The
OPENPOS
output is activated when the auxiliary input contact
POSCLOSE
input is
FALSE and the
POSOPEN
input is TRUE. The
CLOSEPOS
output is activated when the
POSOPEN
input is FALSE and the
POSCLOSE input is TRUE.
The
INVALIDPOS
output is activated when both auxiliary contacts have the same
value, that is, both are in the same logical level.
7.2.4.2
Inactivity monitoring
The purpose of the inactivity monitoring is to indicate if the earthing switch or
disconnector has not been operated for a long time.
This module calculates the number of days the earthing switch or disconnector has
remained inactive, that is, has stayed in the same open, closed and intermediate
or faulty state. The calculation is done by monitoring the states of the POSOPEN,
POSCLOSE auxiliary contacts. The inactive days INA_DAYS is available in the
monitored data view. For relay retrofit installations, it is possible to initialize
1MRS759142 F
Condition monitoring functions
REX640
Technical Manual
1377
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......