R
X
Load blinder forward area
(Load-out region or Load exporting)
Load blinder reverse area
(Load-in region or Load importing)
Max impedance angle
Min impedance angle
Min impedance angle
Max impedance angle
Nominal impedance
circle
Resistive
reach Fw
Resistive
reach Rv
Load blinder reverse area
(Load-in region or Load importing)
Load blinder forward area
(Load-out region or Load exporting)
Figure 736: Operating sectors for load blinder
The blinder directional operation can be selected with the
Directional mode setting.
The alternatives are "Non-directional", "Forward" and "Reverse" operation.
Forward operation is allowed if
Directional mode is set to “Forward”. If the resistive
part value of positive sequence impedance is higher than
Resistive reach Fw and
the angle of positive sequence impedance stays in the range limited with the
Max
impedance angle and Min impedance angle on forward area, the function output
LB_FORWARD
is activated.
Reverse operation is allowed if
Directional mode is set to “Reverse”. If the resistive
part value of positive sequence impedance exceeds the limitation of
Resistive reach
Rv and the angle of positive sequence impedance stays in the range limited with the
Max impedance angle and Min impedance angle on reverse area, the function output
LB_REVERSE
is activated.
In case
Directional mode is set to “Non-directional”, operation is allowed both
directions according to conditions described above.
Activation of the
BLOCK
input deactivates the function outputs.
5.16.6
Application
Load blinder or load encroachment, function LBRDOB is used to block the
directional overcurrent protection aiming at avoiding incorrect trip in case of heavy
loading condition in network. In general, the active power increases to the level
leading to a high power factor, the network turns into heavy load status, and there
exists risk of incorrect trip for the directional overcurrent protection because of
high level of load current.
The suitability of
Resistive reach Fw and Resistive reach Rv settings will influence
the activation of load blinder function. If
Resistive reach Fw and Resistive reach Rv
are set beyond the network minimal resistive load, the function will not be activated
in the case that the load impedance approaches the network minimal impedance
load. Hence, the absolute values of
Resistive reach Fw and Resistive reach Rv should
be set less than that of the minimal resistive load.
1MRS759142 F
Protection related functions
REX640
Technical Manual
1297
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......