
The function is internally blocked if any phase current is higher than the set
Max operate current. When the internal blocking activates, the
FAIL
output is
deactivated immediately. The internal blocking is used for avoiding false operation
during a fault situation when the current transformers are saturated due to high
fault currents.
The value of the differential current is available in the monitored data view on
the LHMI or through other communication tools. The value is calculated with the
equation.
I
DIFF
I
A
I
B
I
C
I
REF
_
_
_
_
_
=
+
+
−
(Equation 316)
The
Start value setting is given in units of ×In of the phase current transformer.
The possible difference in the phase and reference current transformer ratios is
internally compensated by scaling
I_REF
with the value derived from the
Primary
current setting values. These setting parameters can be found in the Basic functions
section.
The activation of the
BLOCK
input deactivates the
FAIL
output immediately.
Timer
The timer is activated with the
FAIL
signal. The
ALARM
output is activated after a
fixed 200 ms delay.
FAIL
needs to be active during the delay.
When the internal blocking is activated, the
FAIL
output deactivates immediately.
However, the
ALARM
output deactivates after a fixed delay of three seconds.
The function resets when the differential current is below the start value and the
highest phase current is more than 5 percent of the nominal current (0.05 × In).
If the current falls to zero when the
FAIL
or
ALARM
outputs are active, the
deactivation of these outputs is prevented.
The activation of the
BLOCK
input deactivates the
ALARM
output.
6.2.6
Application
Open or short-circuited current transformer cores can cause unwanted operation
in many protection functions such as differential, earth-fault current and negative-
sequence current functions. When currents from two independent three-phase sets
of CTs or CT cores measuring the same primary currents are available, reliable
current circuit supervision can be arranged by comparing the currents from the two
sets. When an error in any CT circuit is detected, the protection functions concerned
can be blocked and an alarm given.
In case of high currents, the unequal transient saturation of CT cores with a
different remanence or saturation factor can result in differences in the secondary
currents from the two CT cores. An unwanted blocking of protection functions
during the transient stage must then be avoided.
The supervision function must be sensitive and have a short operation time to
prevent unwanted tripping from fast-acting, sensitive numerical protections in case
of faulty CT secondary circuits.
1MRS759142 F
Supervision functions
REX640
Technical Manual
1313
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......