
BLOCK
SWING
OPERATE
Blocking
logic
OSB
Impedance
calculation
Out of step
detection
DISABLE
OSB_Z2
SWING_OP
I
1
I
2
U
1
I3P
U3P
Figure 559: Functional module diagram
Impedance calculation
This module calculates the positive-sequence impedance (Z1) using positive-
sequence voltage and current. For the module to calculate impedance it is required
that the positive-sequence current is above
Min Ps Seq current setting and the
negative-sequence current is below the
Max Ng Seq current setting.
The calculated positive-sequence impedance amplitude Z1_AMPL and angle
Z1_ANGLE are available in ohms and degrees, respectively, in the Monitored data
view.
The calculated impedance is converted to ohms as the operating
characteristics are defined with the ohm settings.
Out of step detection
The operating characteristic is a circular offset mho on the impedance plane with
two pair of blinders. The mho characteristic is defined with the
Forward reach,
Reverse reach, and Impedance angle settings. Forward reach defines the impedance
from the origin to the edge of circle on the top side.
Reverse reach defines the
impedance from the origin to the edge of the circle on the bottom side. The
diameter of the mho characteristics is the sum of
Forward reach and Reverse reach
settings. Two sets of blinders are defined by
Inner blinder R and Outer blinder R
intercepting at R-axis. The blinders are at the same angle as the
Impedance angle.
The second blinder of each outer and inner pair is automatically made symmetrical
with the origin of the R-X plane.
For a correct operation, it is required that the setting for
Inner blinder R
is less than the setting for
Outer blinder R.
The circular mho characteristic can be further divided into two zones by setting
Zone 2 enable to “Yes”. The boundary between zones is set using the setting Zone 1
reach. The lower portion of the circle, Zone 1, is separated from the upper portion,
Zone 2, by a line, perpendicular to the blinders, located at a set percentage of the
Forward reach setting from the origin.
1MRS759142 F
Protection functions
REX640
Technical Manual
1007
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......