
Flt loop resistance
R
R
fault
=
+
1
2
(Equation 300)
Flt loop reactance
Flt phase reactance
X
=
=
1
(Equation 301)
Figure 686: Fault loop impedance for phase-to-phase fault loops (either “AB Fault”,
“BC Fault” or “CA Fault”)
The fault distance calculation algorithm for the phase-to-phase fault loops is
defined by using settings
Load Com PP loops and Enable simple model. Options
for the selection are "Disabled" or "Enabled".
Load compensation can be enabled or disabled with setting
Load Com PP loops.
Load compensation should be disabled only if the ratio between the fault current
and load current is high or when the value of the fault distance estimate for the
short circuit fault is required from each shot of an autoreclosing sequence.
The fault distance calculation is most accurate when calculated with the fault loop
model. This model requires positive-sequence impedances of the protected feeder
to be given as settings. If these settings are not available, valid impedance values
can be calculated also without the fault loop model with setting
Enable simple
model = "Enabled". However, a valid distance estimate, that is, the conversion
of measured impedance (“electrical fault distance’’) into a physical fault distance
requires accurate positive-sequence impedance settings.
Fault loop “ABC Fault”
Fault loop “ABC Fault” is used exclusively for the three-phase short circuit fault.
shows the three-phase fault loop model. The following impedances are
measured and stored in the recorded data of SCEFRFLO.
Flt point resistance
R
fault
=
(Equation 302)
Flt loop resistance
R
R
fault
=
+
1
(Equation 303)
Flt loop reactance
Flt phase reactance
X
=
=
1
(Equation 304)
Protection related functions
1MRS759142 F
1204
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......