Operation mode
Parallel mode
MSTR_TRIGG
OPR_MODE_STS
Auto parallel
Input control Com-
mand
0
1
Auto follower
Auto parallel
Input control Com-
mand
1
1
Auto master
Table 1572: Active operation mode when Operation mode setting is "Input control"
or "Command"
PARALLEL
AUTO
Parallel mode
MSTR_TRIGG
OPR_MODE_STS
0
0
–
–
Manual
0
1
–
–
Auto single
1
0
Master
–
Parallel manual
1
0
Follower
–
Manual
1
0
MCC
–
Manual
1
0
NRP
–
Manual
1
0
Input control
Command
0
1
Manual
1
0
Input control
Command
1
1
Parallel manual
1
1
Master
–
Auto master
1
1
Follower
–
Auto follower
1
1
MCC
–
MCC
1
1
NRP
–
NRP
1
1
Input control
Command
0
1
Auto follower
1
1
Input control
Command
1
1
Auto master
The active operation mode can be read from the monitored data OPR_MODE_STS.
Command exclusion
An active operation mode change using three inputs (
PARALLEL
,
AUTO
,
MSTR_TRIGG
and setting group change either by input or via menu) is needed when the active
operation mode must be changed automatically, that is, there is a logic which drives
these three inputs based on the status information from the circuit breakers.
The common Local/Remote (L/R) exclusion concerns the manual raise and lower
commands of OL5ATCC, that is, it internally provides the exclusion mechanism to
prevent remote commands (from SCADA) when the protection relay is in local mode
and vice versa.
9.10.5.4
Manual voltage regulation
The manual raising and lowering commands can be given via the configuration
inputs
LOWER_LOCAL
and
RAISE_LOCAL
, via the HMI of the protection relay or via
1
The master role is set on rising edge and internally kept until another parallel transformer
assumes the master role, or the operation mode is changed.
Control functions
1MRS759142 F
1700
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......