
Max Dur delta Calc (maximum duration for delta calculation). After this time is
elapsed from initial fault detection moment, then the validity of delta-calculation
is not considered to be valid anymore and thus fault current estimation is done
without delta calculation i.e. based on real time measurement of threefold negative-
sequence component (
). The memorized pre-fault negative-sequence
component values are reset when function is reset.
In practical compensated networks, earth-fault current may include a large share of
harmonic components, especially during low ohmic faults. In IFPTOC the estimation
of earth-fault (EF) current can be done with or without harmonic components.
Refer to Figure 5 for illustrating the effect of harmonics on earth-fault current
estimate. Measurement of harmonic components can be enabled with setting
Enable harmonics = “Enable”, “Disable”.
Fundamental frequency component is always included into fault current
magnitude estimation, even when setting
Enable harmonics = “Disable”.
When setting
Enable harmonics = “Enable”, the included harmonics are
(if their magnitudes are sufficient for an accurate measurement): 2
nd
, 3
rd
,
5
th
, 7
th
and 9
th
.
Figure 338: Illustration of earth-fault current estimate with and without harmonics calculation enabled
(zoomed view on right hand column)
The harmonic components are only included in the earth-fault current estimate if
their magnitudes are sufficient for an accurate measurement i.e. their values exceed
minimum predefined value (0.3% from I
n
). Also, the effect of harmonics is only taken
into account, if the magnitude of fundamental frequency fault current estimate or
touch voltage exceeds set start thresholds.
For the earth-fault current estimate magnitude,
, can be written:
When setting
Enable harmonics = “Disable”:
1MRS759142 F
Protection functions
REX640
Technical Manual
591
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......