physical fault distance conversion done in the protection relay, especially in cases
where the line impedance non-homogeneity is severe. Each section is enabled by
entering a section length, which differs from zero, to settings
Line Len section A,
Line Len section B or Line Len section C in the order section A-> section B-> section
C.
The impedance model with one line section is enabled by setting
Line Len section
A to differ from zero. In this case the impedance settings R1 line section A, X1 line
section A, R0 line section A and X0 line section A are used for the fault distance
calculation and for conversion from reactance to physical fault distance. This option
should be used only in the case of a homogeneous line, that is, when the protected
feeder consists of only one conductor type.
The impedance model with two line sections is enabled by setting both
Line Len
section A and Line Len section B to differ from zero. In this case the impedance
settings
R1 line section A, X1 line section A, R0 line section A, X0 line section A, R1
line section B, X1 line section B, R0 line section B and X0 line section B are used
for the fault distance calculation and for conversion from reactance to physical fault
distance. This option should be used in the case of a non-homogeneous line when
the protected feeder consists of two types of conductors.
The impedance model with three line sections is enabled by setting
Line Len section
A, Line Len section B and Line Len section C to differ from zero. In this case, the
impedance settings
R1 line section A, X1 line section A, R0 line section A, X0 line
section A, R1 line section B, X1 line section B, R0 line section B, X0 line section B,
R1 line section C, X1 line section C, R0 line section C and X0 line section C are used
for the fault distance calculation and for conversion from reactance to physical fault
distance. This option should be used in the case of a non-homogeneous line when
the protected feeder consists of more than two types of conductors.
The effect of line impedance non-homogeneity on the conversion of fault loop
reactance into physical fault distance is demonstrated in the example shown in
with a 10-km-long feeder with three line types. The total line impedance
for the 10 km line is R1 = 6.602 Ω (0.660 Ω/km) and X1 = 3.405 Ω (0.341 Ω/km),
consisting of the following sections and impedance values.
• 4 km of PAS 150 (R1 = 0.236 Ω/km, X1 = 0.276 Ω/km)
• 3 km of Al/Fe 54/9 Raven (R1 = 0.536 Ω/km, X1 = 0.369 Ω/km)
• 3 km of Al/Fe 21/4 Swan (R1 = 1.350 Ω/km, X1 = 0.398 Ω/km)
The non-homogeneity of feeder impedance can be illustrated by drawing the
protected feeder in RX-diagram (in the impedance plane), as shown in
Protection related functions
1MRS759142 F
1212
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......