
measured residual current Io. The phase angle of operation point in the
faulted feeder can be approximated with equation
ϕ
=
+
atan
detuning
I
I
I
EFFd
damping
(Equation 96)
I
EFFd
Earth-fault current produced by the protected feeder [A]
I
detuning
Detuning of the arc suppression coil [A]
I
damping
System damping [A]
Example 1:
I
EFFd
= 30 A, I
detuning
= +10 A and I
damping
= 10 A. From
, j = 76 deg. Thus
Tilt angle should not exceed ~10 deg.
Example 2:
I
EFFd
= 50 A, I
detuning
= +10 A and I
damping
= 5 A. From
, j = 85 deg. Thus
Tilt angle should not exceed ~3 deg. However, such a low Tilt angle setting may
endanger the security of protection due to measurement errors of the CBCTs. In this
case, the phase angle of operation point should be increased by considering:
1. System damping increase by increasing the current value of the parallel resistor
of the coil.
2. Reduction of the earth-fault current produced by the protected feeder by, for
example, installation of distributed compensation coils or by change of the
feeder topology.
3. Reduction of overcompensation of the network. The recommendation is to use
the undercompensation mode.
The
DIRECTION
output indicates on which operating sector the current is
measured. The
FAULT_DIR
output indicates in which operation sector the fault
current is measured. The output is operational once the function is started.
To adapt the fault direction determination to possible fault direction change during
the fault, for example, during manual fault location process, a cyclic accumulation
of sum admittance phasors is conducted. The duration of this directional evaluation
cycle is 1.2 ·
Reset delay time (minimum of 600 ms). If the fault direction based
on the cyclic phasor accumulation is opposite to the function direction output for
Reset delay time or 500 ms (minimum of 500 ms), the function is reset and fault
direction calculation of MFADPSDE is restarted.
If the earth-fault protection generates alarms, MFADPSDE also includes a
RESET
input which can be used to externally re-trigger the fault direction determination if
reevaluation of fault direction during a persistent earth fault is required.
It is also recommended to connect the start signal of non-directional earth fault
protection (EFxPTOC), set to operate in case of a cross-country fault, to
RESET
input or
BLOCK
input of MFADPSDE to reset phasor accumulation during a cross-
country fault. MFADPSDE can then adapt to a fault direction change more rapidly if a
singlephase earth fault persists in the system after the other faulty feeder has been
tripped (the cross-country fault has been transformed into a single-phase earth
fault).
The direction of MFADPSDE is supervised by a settable current magnitude
threshold, setting
Min operate current. The operate current used in the magnitude
supervision is measured with a special filtering method, which provides a stable
Protection functions
1MRS759142 F
562
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......