8.1.9.3
Functionality
The residual voltage measurement function RESVMMXU provides limit value
supervision output (
HIGH_ALARM
,
HIGH_WARN
). Setting parameters
On delay time
and
Off delay time are used for controlling the activation and, respectively, the
deactivation of alarm and warning outputs.
Instantaneous residual voltage in volt is available for application configurations
through output
U_INST_RES
. The residual voltage demand value in volt is for
connecting to Load profile recorder (LDPRLRC) through output
U_DMD_RES
.
8.1.9.4
Analog channel configuration
RESVMMXU has one analog group input which must be properly configured.
Table 1400: Analog inputs
Input
Description
URES
Residual voltage (measured or calculated)
See the preprocessing function blocks in this document for the possible
signal sources.
There are a few special conditions which must be noted with the configuration.
Table 1401: Special conditions
Condition
Description
URES calculated
The function requires that all three voltage
channels are connected to calculate residu-
al voltage. Setting
VT connection
must be
"Wye" in that particular UTVTR.
Improper analog channel configuration causes a validation error if the analog
channels are not completely configured or they do not match with certain settings.
For troubleshooting, check the contents of this chapter and also the preprocessing
blocks in this document. The configuration can be written to the protection relay
once the mismatch is corrected.
8.1.9.5
Signals
RESVMMXU Input signals
Table 1402: RESVMMXU Input signals
Name
Type
Default
Description
URES
SIGNAL
-
Residual voltage
BLOCK
BOOLEAN
0=False
Block signal for all bi-
nary outputs
Measurement functions
1MRS759142 F
1466
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......