Vector group of
the transformer
Winding 1 type Winding 2 type
Clock number
Zro A
Elimination
ZNy1
ZN
y
Clk Num 1
Not needed
Zy5
Z
y
Clk Num 5
Not needed
Zyn5
Z
yn
Clk Num 5
Not needed
ZNyn5
ZN
yn
Clk Num 5
HV side
ZNy5
ZN
y
Clk Num 5
Not needed
Zy7
Z
y
Clk Num 7
Not needed
Zyn7
Z
yn
Clk Num 7
Not needed
ZNyn7
ZN
yn
Clk Num 7
HV side
ZNy7
ZN
y
Clk Num 7
Not needed
Yy0
Y
y
Clk Num 0
Not needed
Commissioning
The correct settings, which are
CT connection type, Winding 1 type, Winding 2
type and Clock number, for the connection group compensation can be verified
by monitoring the angle values
I_ANGL_A1_B1
,
I_ANGL_B1_C1
,
I_ANGL_C1_A1
,
I_ANGL_A2_B2
,
I_ANGL_B2_C2
,
I_ANGL_C2_A2
,
I_ANGL_A1_A2
,
I_ANGL_B1_B2
and
I_ANGL_C1_C2
while injecting the current into the transformer. These angle
values are calculated from the compensated currents. See signal description from
Monitored data table.
When a station service transformer is available, it can be used to provide current
to the high voltage side windings while the low voltage side windings are short-
circuited. This way the current can flow in both the high voltage and low voltage
windings. The commissioning signals can be provided by other means as well. The
minimum current to allow for phase current and angle monitoring is 0.015 I
r
.
Figure 400: Low voltage test arrangement. The three-phase low voltage source can
be the station service transformer.
The
Tapped winding control setting parameter has to be set to “Not in use” to make
sure that the monitored current values are not scaled by the automatic adaptation
to the tap changer position. When only the angle values are required, the setting
of
Tapped winding is not needed since angle values are not affected by the tap
changer position adaptation.
1MRS759142 F
Protection functions
REX640
Technical Manual
705
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......