Table 1531: Typical delays for different output types
Output type
Recommended value for T
PL
Both Bus side
voltage measurements: Non-
Adaptive or
Both Bus side voltage
measurements: Adaptive
Any one of the Bus
side voltage measurement:
Adaptive,
The other Bus side voltage
measurement: Non Adaptive
Semiconductor output (SPO) 16 ms
7 ms
Mechanical relay output
(POSP, PODP)
23 ms
13 ms
The
Minimum Syn time setting defines the minimum time for which synchro check
conditions must be simultaneously fulfilled.
The frequency slip acceleration (ds/dt) SLIP_ACCL is the average value of frequency
slip difference (Δs) calculated over a time period of 0.5 s.
Frequency slip(s)
=
−
(
)
f
f
f
BusA
BusB
BusA
(Equation 371)
The measured bus A voltage (U
BusA
), bus A frequency (f
BusA
), measured bus B
voltage (U
BusB
), bus B frequency (f
BusB
) and phase angle difference (PH_DIFF_MEAS)
values between the two sides of the CB are available as monitored data values.
If the measured U_DIFF_MEAS does not fulfill the condition given in
and thus synchronism is prevented, the monitored data U_DIFF_SYNC is
activated. Similarly PH_DIF_SYNC and FR_DIFF_SYNC are activated based on the
measurements PH_DIFF_MEAS and FR_DIFF_MEAS, respectively. These monitored
data values are updated only when the setting
Synchrocheck mode is set to either
"Synchronous" or "Asynchronous" and the measured ENERG_STATE is "Both Live".
The outputs
U_DIFF
and
FR_DIFF_MEAS
give the calculated phaseto- phase voltage
difference and the frequency difference values, respectively. These
U_DIFF
and
FR_DIFF_MEAS
outputs are sent to ASCGAPC.
The monitored data ACT_ASC_CB indicates the ASCGAPC CB number. The CB
number of the protection relay's ASCGAPC is received via
ASC1_NS_DAT
signal.
Close CB condition
If
Synchrocheck mode is set to "Asynchronous", the CB close command is generated
as explained below.
From the frequency slip s, the acceleration ds/dt, the bus frequency FR_BUS_MEAS
(f
Bus
) and the set
Closing time of CB, the function calculates the necessary lead
angle (α
Lead
) by which the close CB command is shifted forward in time so that the
main contacts close on phase coincidence.
Control functions
1MRS759142 F
1594
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......