
PH
DIFF
MEAS
U
U
BusA
BusB
_
_
Phase shift
= ∠
− ∠
+
(Equation 368)
∠ U
BusA
Measured bus A side voltage phase angle
∠ U
BusB
Measured bus B side voltage phase angle
Phase shift Setting
Phase shift
The calculated voltage and phase angle difference values between these voltages
are available as monitored data U_DIFF_MEAS and PH_DIFF_MEAS. The setting
Phase shift is used to compensate the angle shift caused if a power transformer
is located between the voltage measurements.
The synchronism condition and CB closing instance are checked according to
several criteria.
• The measured bus A and bus B voltages are higher than the set value of
Live bus
voltage (ENERG_STATE equals “Both Live”).
• The measured bus A and bus B frequencies are both within the range of 95...105
% of the value of the nominal frequency (f
n
).
• The measured bus A and bus B voltages are lower than the set value of
Max
energizing V.
When the
Synchrocheck mode setting parameter is set to "Command",
then the “Synchronous”, “Asynchronous” or “Off” condition of the
network across the CB can be set using the
SynchroChk Mod Ctl control
command only. If the
Synchrocheck mode setting parameter is not set to
"Command", then the
Synchrocheck mode setting parameter is used to
set the “Synchronous”, “Asynchronous” or “Off” condition of the network
across the CB.
Some additional conditions must be fulfilled according to the set
Synchrocheck
mode.
Table 1530: Additional conditions for the synchro check
Measurements
Synchrocheck mode
“Synchronous”
“Asynchronous”
U_DIFF_MEAS
< 0.01 x Nominal voltage (U
n
) < Difference voltage
PH_DIFF_MEAS
< 5 degree
< Difference angle
FR_DIFF_MEAS
< 0.001 x Nominal frequency
(f
n
)
< Frequency difference
Estimated closing angle
N/A
< Difference angle
Control functions
1MRS759142 F
1592
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......