4.3.8.5
Operation principle
The function can be enabled and disabled with the
Operation setting. The
corresponding parameter values are "On" and "Off".
The operation of MHZPDIF can be described using a module diagram. All the
modules in the diagram are explained in the next sections.
OPERATE
START
BLOCK
t
Timer
Level
detector
I3P
I_A
I_B
I_C
Figure 459: Functional module diagram
Level detector
This module compares the three-phase differential currents to the set
Operate
value. If any of the differential currents ID_A, ID_B or ID_C exceeds the set Operate
value, the Level detector module sends an enable signal to the Timer module to
start the definite timer (DT).
Timer
Once activated, the Timer activates the
START
output. The Timer characteristic is
according to DT. When the operation timer has reached the value set by
Minimum
operate time, the
OPERATE
output is activated. If the fault disappears before
the module operates, the reset timer is activated. If the reset timer reaches the
value set by
Reset delay time, the operation timer resets and the
START
output is
deactivated.
The Timer calculates the start duration value START_DUR, which indicates the
percentage ratio of the start situation and the set operation time. The value is
available in the Monitored data view.
The activation of the
BLOCK
signal resets the Timer and deactivates the
START
and
OPERATE
outputs.
4.3.8.6
Application
MHZPDIF provides the winding short circuit and earth-fault protection for motors.
The high-impedance or flux-balance principle has been used through many years for
differential protection due to the capability to manage through-faults with a heavy
current transformer (CT) saturation.
High-impedance principle
The high-impedance principle is stable for all types of faults outside the protection
zone. The stabilization is obtained by a stabilizing resistor in the differential circuit.
This method requires all the CTs to have a similar magnetizing characteristic,
same ratio and a relatively high knee point voltage. The CTs in each phase are
connected in parallel with a relay measuring branch. The measuring branch is a
series connection of the stabilizing resistor and the protection relay.
The stability of the protection is based on the use of the stabilizing resistor (R
s
)
and the fact that the impedance of the CT secondary quickly decreases as the CT
1MRS759142 F
Protection functions
REX640
Technical Manual
807
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......