The sampling latency S
d
is calculated for each telegram on both ends. The
algorithm assumes that the one-way propagation delay P
d
is equal for both
directions.
The echo method without GPS can be used in telecommunication transmission
networks as long as delay symmetry exists, that is, the sending and receiving delays
are equal.
6.4.6
Signals
6.4.6.1
PCSITPC Output signals
Table 1270: PCSITPC Output signals
Name
Type
Description
OK
BOOLEAN
Protection communication ok
WARNING
BOOLEAN
Protection communication
warning
ALARM
BOOLEAN
Protection communication
alarm
COMM
BOOLEAN
Communication detected, ac-
tive when data is received
6.4.7
PCSITPC Settings
Table 1271: PCSITPC Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Reset delay time
100...300000
ms
10
1000
Reset delay time
from alarm and
warning into ok
state
Alarm count
0...99999
1
0
Set new alarm
count value
Warning count
0...99999
1
0
Set new warning
count value
6.4.8
PCSITPC Monitored data
Table 1272: PCSITPC Monitored data
Name
Type
Values (Range)
Unit
Description
HEALTH
Enum
1=Ok
2=Warning
3=Alarm
-2=Waiting
Communication link
health
ALARM_CNT
INT32
0...99999
Number of alarms de-
tected
Table continues on the next page
Supervision functions
1MRS759142 F
1330
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......