4.1.2.7
Directional overcurrent characteristics
The forward and reverse sectors are defined separately. The forward operation area
is limited with the
Min forward angle and Max forward angle settings. The reverse
operation area is limited with the
Min reverse angle and Max reverse angle settings.
The sector limits are always given as positive degree values.
In the forward operation area, the
Max forward angle setting gives the
counterclockwise sector and the
Min forward angle setting gives the corresponding
clockwise sector, measured from the
Characteristic angle setting.
In the backward operation area, the
Max reverse angle setting gives the
counterclockwise sector and the
Min reverse angle setting gives the corresponding
clockwise sector, a measurement from the
Characteristic angle setting that has
been rotated 180 degrees.
Figure 209: Configurable operating sectors
Table 393: Momentary per phase direction value for monitored data view
Criterion for per phase direction information
The value for DIR_A/_B/_C
The ANGLE_X is not in any of the defined sectors, or the direc-
tion cannot be defined due too low amplitude
0 = unknown
The ANGLE_X is in the forward sector
1 = forward
Table continues on the next page
1MRS759142 F
Protection functions
REX640
Technical Manual
351
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......