Blocking inputs
Description
BLOCK
When active (TRUE), the operation of the function is blocked;
only measurement value outputs are updated.
BLK_OPR_LS
When active (TRUE), TR3PTDF acts normally except that the
OPR_LS
output is not active or activated in any circumstan-
ces. Additionally, the
OPERATE
output can be activated only
by the instantaneous high stage (if not blocked).
BLK_OPR_HS
When active (TRUE), TR3PTDF acts normally except that the
OPR_HS
output is not active or activated in any circumstan-
ces. Additionally, the
OPERATE
output can be activated only
by the biased low stage (if not blocked).
4.3.3.6
Current transformer connections and transformation ratio
correction
The combinations of the connections of the primary current transformers are
designated as "Type 1" and "Type 2". The type needs to be selected separately
for the combination of CT connections on the winding 1 and 2 sides as well as
for the combination of CT connections on the winding 1 and 3 sides in case of
three-winding transformer.
• If the positive directions of the winding 1 and winding 2 relay currents are
opposite, the setting parameter
CT connection 1-2 is "Type 1", as shown in
.
• If the positive directions of the winding 1 and winding 2 relay currents are equal,
the setting parameter
CT connection 1-2 is "Type 2", as shown in
• 'The default value of the
CT connection 1-2 settings is "Type 1".
• The same applies for the
CT connection 1-3 settings.
Protection functions
1MRS759142 F
730
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......