Operation mode
Description
Freq< OR df/dt
A parallel operation between the protection methods is en-
abled. The
START
output is activated when either of the
measured values of the protection module exceeds its set
value. Detailed information about the active module is availa-
ble at the
STR_UFRQ
and
STR_FRG
outputs. The shortest
operate delay time from the set
Operate Tm Freq
or
Oper-
ate Tm df/dt
is dominant regarding the
OPERATE
output.
The time characteristic is according to DT. The characteristic
that activates the
OPERATE
output can be seen from the
OPR_UFRQ
or
OPR_FRG
output. If the frequency gradient
restores before the module operates, the reset timer is acti-
vated. If the timer reaches the value set by the
Reset delay
Tm df/dt
setting, the operate timer resets and the
STR_FRG
output is deactivated. If the frequency restores before the
module operates, the reset timer is activated. If the timer
reaches the value set by the
Reset delay Tm Freq
setting, the
operate timer resets and the
STR_UFRQ
output is deactiva-
ted.
Freq> OR df/dt
A parallel operation between the protection methods is en-
abled. The
START
output is activated when either of the
measured values of the protection module exceeds its set
value. A detailed information from the active module is avail-
able at the
STR_OFRQ
and
STR_FRG
outputs. The shortest
operate delay time from the set
Operate Tm Freq
or
Oper-
ate Tm df/dt
is dominant regarding the
OPERATE
output.
The time characteristic is according to DT. The characteristic
that activates the
OPERATE
output can be seen from the
OPR_OFRQ
or
OPR_FRG
output. If the frequency gradient
restores before the module operates, the reset timer is acti-
vated. If the timer reaches the value set by the
Reset delay
Tm df/dt
setting, the operate timer resets and the
STR_FRG
output is deactivated. If the frequency restores before the
module operates, the reset timer is activated. If the timer
reaches the value set by the
Reset delay Tm Freq
setting, the
operate timer resets and the
STR_UFRQ
output is deactiva-
ted.
The module calculates the start duration value which indicates the percentage ratio
of the start situation and set operate time (DT). The start duration is available
according to the selected value of the
Operation mode setting.
Table 882: Start duration value
Operation mode in use
Available start duration value
Freq<
ST_DUR_UFRQ
Freq>
ST_DUR_OFRQ
df/dt
ST_DUR_FRG
The combined start duration
START_DUR
indicates the maximum percentage ratio
of the active protection modes. The values are available via the Monitored data view.
Protection functions
1MRS759142 F
924
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......