Table 76: Station authority level “L,S,R” using CONTROL function block
L/R Control
L/R Control status
Control access
R/L button
CTRL.LLN0.LocS
ta
4
CTRL.LLN0.MltL
ev
L/R state
CTRL.LLN0.Loc
KeyHMI
Local user
IEC 61850 client
5
IEC 61850
client
6
CTRL_OFF
FALSE
FALSE
0
CTRL_LOC
FALSE
FALSE
1
x
CTRL_STA
TRUE
FALSE
3
CTRL_REM
7
TRUE
FALSE
3
x
CTRL_REM
FALSE
FALSE
2
x
CTRL_ALL
FALSE
FALSE
0
3.8.7
Station authority level “L,S,S+R,L+S,L+S+R”
Station authority level "L,S,S+R,L+S,L+S+R" adds station control access together
with several different multilevel access scenarios. Control access can also be
simultaneously permitted from local, station or remote location. Simultaneous local,
station or remote control operation is not allowed as one client and location at time
can access controllable objects and they remain reserved until the previously started
control operation is first completed by the client.
IED
IEC 61850
remote
IEC 61850
station
IEC 61850
remote
IEC 61850
remote
IEC 61850
remote
IED
IEC 61850
station
IED
IEC 61850
station
IED
IEC 61850
station
L+S
LOCAL
STATION
S+R
IEC 61850
remote
IEC 61850
remote
IED
IEC 61850
station
IED
IEC 61850
station
OFF
L+S+R
Figure 54: Station authority is “L,S,S+R,L+S,L+S+R”
When station authority level “L,S,S+R,L+S,L+S+R” is used, control access can be
selected using R/L button or CONTROL function block. IEC 61850 data object
CTRL.LLN0.LocSta and CONTROL function block input
CTRL_STA
are applicable for
this station authority level.
“Station” and “Local + Station” control access can be reserved by using R/L
button or CONTROL function block in combination with IEC 61850 data object
CTRL.LLN0.LocSta.
4
Station client reserves the control operating by writing controllable point LocSta.
5
Client IEC 61850 command originator category is remote.
6
Client IEC 61850 command originator category is station.
7
CTRL_STA unconnected in application configuration. Station client reserves the control operating
by writing controllable point LocSta.
Basic functions
1MRS759142 F
140
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......