Figure 907: Example of an auto-initiation sequence with synchronization failure in
the first shot and circuit breaker closing failure in the second shot
In the first shot, the synchronization condition is not fulfilled (
SYNC
is FALSE). When
the auto wait timer elapses, the sequence continues to the second shot. During the
second reclosing, the synchronization condition is fulfilled and the close command
is given to the circuit breaker after the second reclose time has elapsed.
After the second shot, the circuit breaker fails to close when the wait close time has
elapsed. The third shot is started and a new close command is given after the third
reclose time has elapsed. The circuit breaker closes normally and the reclaim time
starts. When the reclaim time has elapsed, the sequence is concluded successful.
9.9.6.2
Sequence
The auto reclose sequence is implemented by using CBBs. The highest possible
amount of CBBs is seven. If the user wants to have, for example, a sequence of three
shots, only the first three CBBs are needed. Using building blocks instead of fixed
shots gives enhanced flexibility, allowing multiple and adaptive sequences.
Each CBB is identical. The
Shot number CBB_ setting defines at which point in the
auto-reclose sequence the CBB should be performed, that is, whether the particular
CBB is going to be the first, second, third, fourth or fifth shot.
During the initiation of a CBB, the conditions of initiation and blocking are checked.
This is done for all CBBs simultaneously. Each CBB that fulfils the initiation
conditions requests an execution.
The function also keeps track of shots already performed, that is, at which point the
auto-reclose sequence is from shot 1 to lockout. For example, if shots 1 and 2 have
already been performed, only shots 3 to 5 are allowed.
Additionally, the
Enable shot jump setting gives two possibilities:
• Only such CBBs that are set for the next shot in the sequence can be accepted
for execution. For example, if the next shot in the sequence should be shot 2, a
request from CBB set for shot 3 is rejected.
• Any CBB that is set for the next shot or any of the following shots can be
accepted for execution. For example, if the next shot in the sequence should
be shot 2, also CBBs that are set for shots 3, 4 and 5 are accepted. In other words,
shot 2 can be ignored.
Control functions
1MRS759142 F
1682
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......