3.13.5
Oscillation suppression
Oscillation suppression is used to reduce the load from the system when a binary
input starts oscillating. A binary input is regarded as oscillating if the number of
valid state changes (= number of events after filtering) during one second is equal
to or greater than the set oscillation level value. During oscillation, the binary input
is blocked (the status is invalid) and an event is generated. The state of the input
will not change when it is blocked, that is, its state depends on the condition before
blocking.
The binary input is regarded as non-oscillating if the number of valid state changes
during one second is less than the set oscillation level value minus the set oscillation
hysteresis value. Note that the oscillation hysteresis must be set lower than the
oscillation level to enable the input to be restored from oscillation. When the input
returns to a non-oscillating state, the binary input is deblocked (the status is valid)
and an event is generated.
Table 99: Oscillation parameters
Parameter
Value
Default
Input osc. level
2...50 events/s
30 events/s
Input osc. hyst
2...50 events/s
10 events/s
3.14
Binary outputs
The protection relay provides a number of binary outputs used for tripping,
executing local or remote control actions of a breaker or a disconnector, and for
connecting the protection relay to external annunciation equipment for indicating,
signalling and recording.
Power output contacts are used when the current rating requirements of the
contacts are high, for example, for controlling a breaker, such as energizing the
breaker trip and closing coils.
The contacts used for external signalling, recording and indicating, the signal
outputs, need to adjust to smaller currents, but they can require a minimum current
(burden) to ensure a guaranteed operation.
The protection relay provides both power output and signal output contacts. To
guarantee proper operation, the type of the contacts used are chosen based on
the operating and reset time, continuous current rating, make and carry for short
time, breaking rate and minimum connected burden. A combination of series or
parallel contacts can also be used for special applications. When appropriate, a
signal output can also be used to energize an external trip relay, which in turn can be
confiugred to energize the breaker trip or close coils.
Using an external trip relay can require an external trip circuit supervision
relay. It can also require wiring a separate trip relay contact back to the
protection relay for breaker failure protection function.
All contacts are freely programmable, except the internal fault output IRF.
1MRS759142 F
Basic functions
REX640
Technical Manual
163
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......