the
Phase mode setting is "Three Phase", the example case does not result in any
activation.
Figure 973: Single-phase interruption for the Phase mode value "Single Phase"
10.3.5.5
Three/single-phase selection variation examples
The provided rules always apply for single-phase (
Phase mode is "Single Phase")
power systems. However, for three-phase power systems (where
Phase mode is
"Three Phase"), it is required that all the phases have to be activated before the
activation of the
START
output. Interruption event indication requires all three
phases to undershoot
Voltage Int set simultaneously, as shown in
the requirement for interruption for "Three Phase" is no longer fulfilled, variation is
indicated as a dip as long as all phases are active.
In case of a single-phase interruption of
Chapter 10.3.5.4 Duration measurement
when there is a dip indicated in another phase but the third phase is not active,
there is no variation indication start when
Phase mode is "Three Phase". In this case,
only the
Phase Mode value "Single Phase" results in the
ST_B
interruption and the
ST_A
dip.
It is also possible that there are simultaneously a dip in one phase and a swell
in other phases. The functionality of the corresponding event indication with one
inactive phase is shown in
. Here, the "Swell + dip" variation type of
Phase
mode is "Single Phase". For the selection "Three Phase" of Phase mode, no event
indication or any activation takes place due to a non-active phase.
1MRS759142 F
Power quality measurement functions
REX640
Technical Manual
1837
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......