U_A
U_C
U_B
DIPST
INTST
SWELLST
Voltage Int set
Voltage dip set
Voltage swell set
FALSE
TRUE
FALSE
TRUE
FALSE
TRUE
DIPST
INTST
SWELLST
FALSE
TRUE
FALSE
TRUE
FALSE
TRUE
A) Three phase mode
B) Single phase mode
Figure 969: Detection of three-phase voltage interruption
The module measures voltage variation magnitude on each phase separately, that
is, there are phase-segregated outputs
ST_A
,
ST_B
and
ST_C
for voltage variation
indication. The configuration parameter
Phase supervision defines which voltage
phase or phases are monitored. If a voltage phase is selected to be monitored, the
function assumes it to be connected to a voltage measurement channel. In other
words, if an unconnected phase is monitored, the function falsely detects a voltage
interruption in that phase.
The maximum magnitude and depth are defined as percentage values calculated
from the difference between the reference and the measured voltage. For example,
a dip to 70 percent means that the minimum voltage dip magnitude variation is 70
percent of the reference voltage amplitude.
The activation of the
BLOCK
input resets the function and outputs.
10.3.5.3
Variation validation
The validation criterion for voltage variation is that the measured total variation
duration is between the set minimum and maximum durations (Either one of
VVa
dip time 1, VVa swell time 1 or VVa Int time 1, depending on the variation type, and
VVa Dur Max). The maximum variation duration setting is the same for all variation
types.
shows voltage dip operational regions. In
, only one voltage
dip/swell/Int set is drawn, whereas in this figure there are three sub-limits for the
dip operation. When
Voltage dip set 3 is undershot, the corresponding
ST_x
and
1MRS759142 F
Power quality measurement functions
REX640
Technical Manual
1833
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......