9.9.2
Function block
Figure 891: Function block
9.9.3
Functionality
About 80 to 85 percent of faults in the MV overhead lines are transient and
automatically cleared with a momentary de-energization of the line. The rest of the
faults, 15 to 20 percent, can be cleared by longer interruptions. The de-energization
of the fault location for a selected time period is implemented through automatic
reclosing, during which most of the faults can be cleared.
In case of a permanent fault, the automatic reclosing is followed by final tripping.
A permanent fault must be located and cleared before the fault location can be
re-energized.
The autoreclosing function DARREC can be used with any circuit breaker suitable for
autoreclosing. The function provides five programmable autoreclosing shots which
can perform one to five successive autoreclosings of desired type and duration, for
instance one high-speed and one delayed autoreclosing.
When the reclosing is initiated with starting of the protection function, the
autoreclosing function can execute the final trip of the circuit breaker in a short
operate time, provided that the fault still persists when the last selected reclosing
has been carried out.
9.9.3.1
Protection signal definition
The
Control line setting defines which of the initiation signals are protection start
and trip signals and which are not. With this setting, the user can distinguish the
blocking signals from the protection signals. The
Control line setting is a bit mask,
that is, the lowest bit controls the
INIT_1
line and the highest bit the
INIT_6
line.
Some example combinations of the
Control line setting are as follows:
Control functions
1MRS759142 F
1662
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......