to be considered in a proper overexcitation protection of the transformer. Also,
measurement for the voltage must not be taken from any winding where OLTC is
located.
It is assumed that overexcitation is a symmetrical phenomenon caused by events
such as loss-of-load. A high phase-to-earth voltage does not mean overexcitation.
For example, in an unearthed power system, a single phase-to-earth fault means
high voltages of the healthy two phases to earth but no overexcitation on any
winding. The phase-to-phase voltages remain essentially unchanged. An important
voltage to be considered for the overexcitation is the voltage between the two ends
of each winding.
Example calculations for overexcitation protection
Example 1
Nominal values of the machine
Nominal phase-to-phase voltage (U
n
)
11000 V
Nominal phase current (I
n
)
7455 A
Nominal frequency (f
n
)
50 Hz
Leakage reactance (X
leak
)
20% or 0.2 pu
Measured voltage and load currents of the machine
Phase A-to-phase B voltage (U
AB
)
11500∠0° V
Phase A current (I
A
)
5600∠-63.57° A
Phase B current (I
B
)
5600∠176.42° A
Measured frequency (f
m
)
49.98 Hz
The setting
Voltage Max Cont
100%
The setting
Voltage selection
phase-to-phase
The setting
Phase supervision
A or AB
The pu leakage reactance X
leakPU
is converted to ohms.
X
X
U
I
Ohms
leak
leakPU
n
n
Ω
=
⋅
⋅
=
⋅
⋅
=
3
0 2
11000
7455
3
0 170378
.
.
(Equation 251)
The internal induced voltage E of the machine is calculated.
E
U
I
I
jX
AB
A
B
leak
=
+
−
⋅
(
) (
)
(Equation 252)
E = 11500∠0°+ (5600∠-63.57°- 5600∠176.42°) · (0.170378∠90°) = 12490 V
The excitation level M of the machine is calculated.
Protection functions
1MRS759142 F
894
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......