in PCM600. Similarly, the
TEMP_RL
output of MPTTR must be connected to the
TEMP_RL
input of this function in Application Configuration in PCM600.
When the emergency start signal
START_EMERG
is set high and if the value of the
cold or warm counter is above its start value setting, the value of the counter is
set one count less than the respective maximum number of start value setting. This
disables
BLK_RESTART
and
OPERATE
which makes the restart of motor possible.
The values can be reset by activating the
RESET
binary input. The activation of the
RESET
input also resets the counter decrease timer. The counter value can also be
reset on the Clear menu.
Limit supervision
This module compares the motor cold and warm count to the set
Max Num cold
start and Max Num warm start, respectively. The
BLK_RESTART
output is activated
when either the cold or the warm start counter reaches the set
Max Num cold start
or
Max Num warm start, respectively. The
OPERATE
output is activated when either
the cold or the warm start counter exceeds the set
Max Num cold start or Max Num
warm start, respectively.
When the
BLK_RESTART
output is active, T_RST_ENA shows the possible time for
the next restart. The value of T_RST_ENA is calculated as the time left for both
counters to decrease below their maximum number of starts.
Activation of the
BLOCK
input blocks both
OPERATE
and
BLK_RESTART
outputs.
6.7.5
Application
Repeated motor starts increase the temperature to a high value in the stator or
rotor windings, or both, unless enough time is allowed for the heat to dissipate.
To ensure a safe operation, it is necessary to provide a fixed-time interval between
starts or limit the number of starts within a period of time. This is why the motor
manufacturers have restrictions on how many starts are allowed in a defined time
interval.
This function counts the number of cold and warm starts and provides a block
restart signal when the number of starts reaches the permitted limit. The customer
can use this signal for blocking a new start operation. An operate signal is also
available which can be used to disconnect the motor when the number of starts
exceeds the limit.
6.7.6
Signals
Supervision functions
1MRS759142 F
1344
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......