fact that the phase angle difference between U
o
and I
o
increases as the
capacitive earth-fault current contribution increases. Phase angle difference
may become so high that correct operation of traditional protection functions
is endangered. This is not the case for IFPTOC, as fault current estimate is not
affected by the capacitive earth-fault current contribution of the protected
feeder itself.
- In case earth fault occurs during abnormal network topologies, or when
fault current compensation is temporarily not effective or when network is
operated heavily over- or under-compensated.
• Magnitude of true fault current is estimated without need on any pre-defined
information on the network topology.
• Also, the effect of fault resistance can be considered and compensated in the
estimated earth-fault current magnitude applying dedicated fault resistance
compensation method. This functionality allows acceleration of protection
operation speed during high(er) ohmic earth fault when actual fault current
magnitude is low.
IFPTOC includes also dedicated protection functionality for important practical
earth-fault scenarios such as switch onto fault (SOTF) condition, for intermittent
earth faults and for high current cross-country earth-faults. Each of such fault
condition can be tripped with individually defined operation criteria enabling high
application flexibility and reliability.
4.2.10.4
Analog channel configuration
IFPTOC has four analog group inputs which must be properly configured.
Table 625: Analog inputs
Input
Description
I3P
Three phase currents
IRES
Residual current (measured or calculated)
U3P
Three phase voltages
URES
Measured or calculated residual voltage
See the preprocessing function blocks in this document for the possible
signal sources.
There are a few special conditions which must be noted with the configuration.
Table 626: Special conditions
Condition
Description
U3P connected real meas-
urements
Recommendation to connect all three phase-to-earth voltage
channels. Alternative is at least two phase-to-earth / phaseto-
phase voltages and measured residual voltage (URES).
URES calculated
Three phase-to-earth voltages must be connected for calcu-
lating the residual voltage. Setting
VT connection
must be
"Wye" in that particular UTVTR.
Improper analog channel configuration causes a validation error if the analog
channels are not completely configured or they do not match with certain settings.
check the contents of this chapter and also the preprocessing blocks in this
Protection functions
1MRS759142 F
584
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......