The operation of the subfunction can be described with a module diagram. All the
modules in the diagram are explained in the next sections.
Figure 782: Functional module diagram for circuit breaker gas pressure alarm
The gas pressure is monitored through the binary input signals
PRES_LO_IN
and
PRES_ALM_IN
.
Timer 1
When the
PRES_ALM_IN
binary input is activated, the
PRES_ALM
alarm is activated
after a time delay set with the
Pressure alarm time setting. The
PRES_ALM
alarm can
be blocked by activating the
BLOCK
input.
Timer 2
If the pressure drops further to a very low level, the
PRES_LO_IN
binary input
becomes high, activating the lockout alarm
PRES_LO
after a time delay set with
the
Pres lockout time setting. The
PRES_LO
alarm can be blocked by activating the
BLOCK
input.
7.1.6
Application
SSCBR includes different metering and monitoring subfunctions.
Circuit breaker status
Circuit breaker status monitors the position of the circuit breaker, that is, whether
the breaker is in an open, closed or intermediate position.
Circuit breaker operation monitoring
The purpose of the circuit breaker operation monitoring is to indicate that the
circuit breaker has not been operated for a long time. The function calculates the
number of days the circuit breaker has remained inactive, that is, has stayed in the
same open or closed state. There is also the possibility to set an initial inactive day.
Breaker contact travel time
High traveling times indicate the need for the maintenance of the circuit breaker
mechanism. Therefore, detecting excessive traveling time is needed. During the
opening cycle operation, the main contact starts opening. The auxiliary contact
A opens, the auxiliary contact B closes and the main contact reaches its opening
position. During the closing cycle, the first main contact starts closing. The auxiliary
contact B opens, the auxiliary contact A closes and the main contact reaches its
1MRS759142 F
Condition monitoring functions
REX640
Technical Manual
1369
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......