Frequency matching in manual mode
If
Auto Syn mode is set to "Manual mode", the frequency raise or lower command
pulses are generated manually from the function's user commands.
If the command Gov frequency raise is set to “RAISE”, the function activates the
frequency raise command pulse
RAISE_F
. If the command Gov frequency lower
is set to “LOWER”, the function activates the frequency lower command pulse
LOWER_F
.
The length of these generated pulses tpf and pulse off interval tsf are based on the
settings as: tpf =
Freq pulse Min Dur; tsf = Freq pulse off Intv.
Frequency matching with variable command pulse lengths
When the setting
Frequency match mode is set to "Variable Pulse", the frequency
matching is done with variable command pulse lengths.
The frequency matcher issues a command with a length proportional to the current
slip. The proportionality factor df/dt can be adapted to the governor. The frequency
matcher aims at a value midway between the nearer slip limit and zero.
The adjusting frequency command pulse length tpf is calculated as
tpf
s
s
df
dt
=
± −
±
max
2
(Equation 363)
s
Measured frequency difference across the CB to be synchronized
+smax
Setting
Freq Diff Ov Synch
-smax
Setting
Freq Diff sub Synch
df/dt
Setting
Freq rate of change
The command length does not fall below a settable minimum value
Freq pulse Min
Dur. After an adjusting command, the system waits for the set Freq pulse off Intv
(tsf) so that the actual values can stabilize to the new set point.
Control functions
1MRS759142 F
1576
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......