Figure 695: An example of the ALARM output use
5.7.5.6
Recorded data
All the information required for a later fault analysis is recorded to SCEFRFLO
recorded data. In the protection relay, recorded data is found in Monitoring >
Recorded data > Other protection > SCEFRFLO.
SCEFRFLO has also monitored data values which are used for the read-out of
continuous calculation values.
shows which of the recorded data values
are available as continuous monitoring values during a fault.
Table 1156: Cross reference table for recorded and monitored data values
Recorded data
Monitored data
Flt loop
FAULT_LOOP
Flt distance
FLT_DISTANCE
Flt Dist quality
FLT_DIST_Q
Flt loop resistance
RFLOOP
Flt loop reactance
XFLOOP
Flt phase reactance
XFPHASE
Flt point resistance
RF
Flt to Lod Cur ratio
IFLT_PER_ILD
Equivalent load Dis
S_CALC
XC0F Calc
XC0F_CALC
5.7.6
Measurement modes
The full operation of SCEFRFLO requires that all three phase-to-earth voltages are
measured. The voltages can be measured with conventional voltage transformers or
voltage dividers connected between the phase and earth (
VT connection is set to
“Wye”). Another alternative is to measure phase-to-phase voltages (
VT connection
is set to “Delta”) and residual voltage (Uo). Both alternatives are covered by setting
the configuration parameter
Phase voltage Meas to "Accurate".
Protection related functions
1MRS759142 F
1216
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......