Figure 376: Operation during test operation of the line differential protection
4.3.1.6
Commissioning
The commissioning of the line differential protection scheme would be difficult
without any support features in the functionality because of the relatively long
distance between the protection relays. This has been taken into consideration in
the design of the line differential protection. The communication channel can be
used for echoing the locally fed current phasors from the remote end. By using this
mode, it is possible to verify that differential calculation is done correctly in each
phase. Also, the protection communication operation is taken into account with the
differential current calculation when this test mode is used.
Required material for testing the protection relay
• Calculated settings
• Terminal diagram
• Circuit diagrams
• Technical and application manuals of the protection relay
• Single of three-phase secondary current source
• Single of three-phase primary current source
• Timer with start and stop interfaces
• Auxiliary voltage source for the protection relays
• PC with related software, a Web browser for WHMI
The setting and configuration of the protection relay must be completed before
testing.
The terminal diagram, available in the technical manual, is a general diagram of the
protection relay.
The same diagram is not always applicable to each specific delivery,
especially for the configuration of all the binary inputs and outputs.
Therefore, before testing, check that the available terminal diagram
corresponds to the protection relay.
1MRS759142 F
Protection functions
REX640
Technical Manual
665
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......