Parameter
Values (Range)
Unit
Step
Default
Description
6=0...20mA
Num of knee points
0...4
0
Number of knee points in scaling
Input maximum
–10000.0...10000.0
10000.0
Maximum analog input value for
mA scaling
Input knee point 4
–10000.0...10000.0
0.0
Input knee point value 4 for scal-
ing
Input knee point 3
–10000.0...10000.0
0.0
Input knee point value 3 for scal-
ing
Input knee point 2
–10000.0...10000.0
0.0
Input knee point value 2 for scal-
ing
Input knee point 1
–10000.0...10000.0
0.0
Input knee point value 1 for scal-
ing
Input minimum
–10000.0...10000.0
–10000.0
Minimum analog input value for
mA scaling
Value maximum
–20.0...20.0
mA
20
Maximum analog output value
for mA output
Value knee point 4
–20.0...20.0
mA
0
Knee point value 4 for output
scaling
Value knee point 3
–20.0...20.0
mA
0
Knee point value 3 for output
scaling
Value knee point 2
–20.0...20.0
mA
0
Knee point value 2 for output
scaling
Value knee point 1
–20.0...20.0
mA
0
Knee point value 1 for output
scaling
Value minimum
–20.0...20.0
mA
–20
Minimum analog output value for
mA output
3.15.8
Monitored data
Table 113: mA Monitored data
IEC name
Type
Values
(Range)
Unit
Description
AI_RANGE
Enum
mA input, range
AI_DB
FLOAT32
mA input, reported value
Table 114: RTD Monitored data
IEC name
Type
Values
(Range)
Unit
Description
AI_RANGE
Enum
RTD input, range
AI_DB
FLOAT32
RTD input, reported value
3.16
SMV function blocks
SMV function blocks are used in the process bus applications with the IEC 61850-9-2
LE protocol. Function blocks represent the sending of the sampled measured values
of analog currents and voltages and the receiving of the sampled values of analog
currents and voltages.
Basic functions
1MRS759142 F
188
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......