On the WHMI, internal fault information is shown under Self-Supervision Status.
Figure 28: Internal fault information on Web HMI
Table 43: Internal fault indications and codes
Fault indication
Fault
code
Additional
information
Fast self-
recovery
attempt
Slow 10min
self-
recovery
(# of
attempts)
Immediate
IRF-mode
Action in permanent fault
state
Internal Fault
System error
2
Start up error:
HW/SW mismatch
No
No
Yes
If relay SW has just been
updated, redo it. If not re-
covered, contact your near-
est ABB representative to
check the next possible
corrective action.
Internal Fault
System error
2
Start up or runtime
error: Data bus er-
ror, CPU module
Yes
Yes (3)
No
Restart the relay. If recov-
ered by restarting, contin-
ue relay normal operation.
If not recover by restart-
ing, replace the relay, most
probably hardware failure
in CPU module.
Internal Fault
System error
2
Start up error: SCL
file missing
No
No
Yes
Do factory restore or re-
write configuration using
PCM600.
Internal Fault
System error
2
Start up error:
Missing order num-
ber
No
No
Yes
Do factory restore. If not
recovered, contact your
nearest ABB representative
to check the next possible
corrective action.
Internal Fault
System error
2
Start up error:
FPGA HW error,
CPU module
Yes
Yes (3)
No
Restart the relay. If recov-
ered by restarting, contin-
ue relay normal operation.
If not recover by restart-
ing, replace the relay, most
probably hardware failure
in CPU module.
Internal Fault
System error
2
Start up error:
FPGA image cor-
rupted, CPU mod-
ule
Yes
Yes (3)
No
Restart the relay or if relay
SW has just been updated,
redo it. If recovered by re-
starting, continue relay nor-
mal operation. If not recov-
ered by restarting or redo-
ing SW update, replace the
relay, most probably hard-
ware failure in CPU module.
Internal Fault
System error
2
Runtime error: CPU
internal fault
Yes
Yes (3)
No
Restart the relay. If recov-
ered by restarting, contin-
ue relay normal operation.
If not recover by restart-
Table continues on the next page
1MRS759142 F
Basic functions
REX640
Technical Manual
101
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......