Parameter
Values (Range)
Unit
Step
Default
Description
Alarm Op number
0...99999
1
200
Alarm limit for
number of opera-
tions
Lockout Op num-
ber
0...99999
1
300
Lock out limit for
number of opera-
tions
Current exponent
0.00...5.00
0.01
2.00
Current exponent
setting for energy
calculation
Difference Cor time -10...10
ms
1
5
Corr. factor for
time dif in aux. and
main contacts open
time
Alm Acc currents
Pwr
0.00...20000.00
0.01
2500.00
Setting of alarm
level for accumula-
ted currents power
LO Acc currents
Pwr
0.00...20000.00
0.01
2500.00
Lockout limit set-
ting for accumula-
ted currents power
Initial CB Rmn life
0...99999
1
5000
Initial value for the
CB remaining life
Rated Op current
100.00...6300.00
A
0.01
1000.00
Rated operating
current of the
breaker
Rated fault current 500.00...99999.00
A
0.01
5000.00
Rated fault current
of the breaker
Op number rated
1...99999
1
10000
Number of opera-
tions possible at
rated current
Op number fault
1...10000
1
1000
Number of opera-
tions possible at
rated fault current
Inactive Alm days
0...9999
1
2000
Alarm limit value of
the inactive days
counter
Travel time Clc
mode
1=From Cmd to Pos
2=From Pos to Pos
2=From Pos to Pos Travel time calcu-
lation mode selec-
tion
Table 1313: SSCBR Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Opening time Cor
-100...100
ms
1
10
Correction factor
for open travel time
in ms
Closing time Cor
-100...100
ms
1
10
Correction factor
for CB close travel
time in ms
Counter initial Val
0...99999
1
0
The operation num-
bers counter initial-
ization value
Ini Acc currents Pwr 0.00...20000.00
0.01
0.00
Initial value for ac-
cumulation energy
(Iyt)
Life alarm level
0...99999
1
500
Alarm level for CB
remaining life
Pressure alarm
time
0...60000
ms
1
10
Time delay for gas
pressure alarm in
ms
Pres lockout time
0...60000
ms
10
10
Time delay for gas
pressure lockout in
ms
Ini inactive days
0...9999
1
0
Initial value of the
inactive days coun-
ter
Inactive Alm hours
0...23
h
1
0
Alarm time of the
inactive days coun-
ter in hours
Condition monitoring functions
1MRS759142 F
1374
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......