PULSE_INPUT
RESET
FREEZE_COUNT
VALUE_READ
Scaling
Pulse
counter
COUNT_SAT
READ_VALUE
Figure 148: Functional module diagram
Pulse counter
This module counts the number of pulses available at PULSE_INPUT. The count value
is incremented depending upon
Count criteria setting.
Table 250: Relation between setting Count criteria and count value behavior
Count criteria
values
PULSE_INPUT count value
Rising edge
Count value is incremented on the rising edge of PULSE_IN-
PUT.
Falling edge
Count value is incremented on the falling edge of PULSE_IN-
PUT.
On change
Count value is incremented each time a rising edge or falling
edge is available at PULSE_INPUT.
Freeze
Counting is frozen.
The count value is available at COUNT_VALUE in the Monitored data view and is
stored in a nonvolatile memory. This output is updated cyclically and sent to the
station HMI over various communication protocols, depending on the Reporting
interval setting. The start of
Reporting interval corresponds to the start of the
function operation in the protection relay.
Binary output
VALUE_READ
activates for a fixed 200 ms each time the reporting
timer completes its cycle. It is also possible to update COUNT_VALUE before
completion of
Reporting interval and make it available for communication
by providing a minimum 1-second-long pulse at
READ_VALUE
input. Besides
COUNT_VALUE activation,
READ_VALUE
also activates output
VALUE_READ
for 200
ms.
The activation of RESET resets COUNT_VALUE to zero. Activation of FREEZE_COUNT
freezes further counting.
Changing
Count criteria does not reset COUNT_VALUE.
Scaling
This module scales the count value available at COUNT_VALUE. The scaling depends
on the
Unit selection setting. When the function is used for general-purpose
counting,
Unit selection is set as "Count" and the count value is multiplied by the
Pulse quantity setting to calculate the scaled value.
Basic functions
1MRS759142 F
266
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......