
Slope section
I
I
d
b
2
100
2
2
=
⋅
%
(Equation 204)
Slope section
I
I
d
b
3
100
3
3
=
⋅
%
(Equation 205)
The end of the first section
End section 1 can be set at a desired point within the
range of 0 to 100 percent (or % I
r
). Accordingly, the end of the second section
End
section 2 can be set within the range of 100 percent to 300 percent (or % I
r
).
The slope of the operating characteristic for the function block varies in different
parts of the range.
In section 1, where 0.0 < I
b
/I
n
<
End section 1, the differential current required for
tripping is constant. The value of the differential current is the same as the
Low
operate value setting selected for the function block. The Low operate value setting
allows for small inaccuracies of the current transformers but it can also be used to
influence the overall level of the operating characteristic.
Section 2, where
End section 1 < I
b
/I
n
<
End section 2, is called the influence area
of the setting
Slope section 2. In this section, variations in End section 2 affect the
slope of the characteristic, that is, how big the change in the differential current
required for tripping is in comparison to the change in the load current. The
End
section 2 setting allows for CT errors.
In section 3, where I
b
/I
n
>
End section 2, the slope of the characteristic can be
set by
Slope section 3 that defines the increase in the differential current to the
corresponding increase in the biasing current.
The required differential current for tripping at a certain stabilizing current level can
be calculated using the formulae:
For a stabilizing current lower than
End section 1
I
I
Set Low operate value
doperate
r
[%
]
=
(Equation 206)
For a stabilizing current higher than
End section 1 but lower than End section 2
I
I
Low operate value
I
Ir
End section
Slope
doperate
r
b
[%
]
(
[%
]
)
=
+
−
⋅
1
ssection
2
(Equation 207)
For higher stabilizing current values exceeding
End section 2
I
I
Low operate value
End section
End section
S
d operate
r
[%
]
(
)
=
+
−
⋅
2
1
llope section
I
I
End section
Slope section
b
r
2
2
3
+
−
⋅
(
[%
]
)
(Equation 208)
When the differential current exceeds the operating value determined by the
operating characteristics, the
OPR_LS
output is activated. The
OPERATE
output is
always activated when the
OPR_LS
output activates.
The operate signal due to the biased stage can be blocked by the activation of the
BLK_OPR_LS
or
BLOCK
input. Also, when the operation of the biased low stage is
Protection functions
1MRS759142 F
792
REX640
Technical Manual
Содержание RELION REX640
Страница 1: ... RELION PROTECTION AND CONTROL REX640 Technical Manual ...
Страница 2: ......
Страница 3: ...Document ID 1MRS759142 Issued 2023 02 07 Revision F Copyright 2023 ABB All rights reserved ...
Страница 167: ...Figure 62 Signal outputs in power supply module 1MRS759142 F Basic functions REX640 Technical Manual 167 ...
Страница 184: ...Figure 84 mA channels working as mA outputs Basic functions 1MRS759142 F 184 REX640 Technical Manual ...
Страница 1868: ...Figure 989 ANSI extremely inverse time characteristics General function block features 1MRS759142 F 1868 REX640 Technical Manual ...
Страница 1869: ...Figure 990 ANSI very inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1869 ...
Страница 1870: ...Figure 991 ANSI normal inverse time characteristics General function block features 1MRS759142 F 1870 REX640 Technical Manual ...
Страница 1874: ...Figure 995 ANSI long time inverse time characteristics General function block features 1MRS759142 F 1874 REX640 Technical Manual ...
Страница 1875: ...Figure 996 IEC normal inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1875 ...
Страница 1876: ...Figure 997 IEC very inverse time characteristics General function block features 1MRS759142 F 1876 REX640 Technical Manual ...
Страница 1877: ...Figure 998 IEC inverse time characteristics 1MRS759142 F General function block features REX640 Technical Manual 1877 ...
Страница 1878: ...Figure 999 IEC extremely inverse time characteristics General function block features 1MRS759142 F 1878 REX640 Technical Manual ...
Страница 1882: ...Figure 1002 RI type inverse time characteristics General function block features 1MRS759142 F 1882 REX640 Technical Manual ...
Страница 1885: ...Figure 1004 UK rectifier inverse time characteristic 1MRS759142 F General function block features REX640 Technical Manual 1885 ...
Страница 1959: ......